Study and Simulation of Voltage Profile Recovery on a 200 km Transmission Line Using Shunt Static Var Compensator (SVC)
DOI:
https://doi.org/10.31686/ijier.vol7.iss11.1965Keywords:
voltage regulation, facts, transmission lines, reactive powerAbstract
This article aims to clarify how Flexible Alternating Current Transmission Systems (FACTS) technology, for static operating devices, conditioned on application to long-distance transmission lines can solve problems related to voltage drop on paths known as “weak zones” of the power transmission system. Some technical aspects of the construction of the SVC Static Reactive Compensator in conjunction with thyristor switching devices such as TCR and TSC are described. The proposed scenario is similar to the Brazilian interconnected system, where much of the generator park is hundreds of miles from the country's major consumer centers, leading to the structure of this system longer transmission lines and consequently greater losses in the transmission paths. For the proposed simulations the MATLAB Simulink ® environment was used considering different voltage unbalance operating ranges caused by three-phase faults in the transmission lines. The conclusions show that the distance from the lines to the load has a great influence on the oscillatory effects of voltage, and the fact that the “loading” transmission lines can compensate for much of the path by generating wars through the circuit's natural capacitance. The allocation of capacitor and shunt reactor banks is a reliable option for the transmission system and can act as a support mechanism for voltage control maneuvers to circumvent abrupt changes in reactive demand. From the simulations output comparison, the transient effects showed greater stability in the voltage signal recovery in the stretches where the compensation blocks were located near the lowering substation bus, thus demonstrating the capacity of the applied technology.
Downloads
References
[2] D. D. L. SILVA, Implementação de Modelo de Controladores FACTS em um Programa de Fluxo; Capacitor Série Controlado a Tiristor e CompensadorSíncronoEstático, UFMA, São Luís, 2018, pp. 22 – 46.
[3] E. R. ROPELATTO, F. D FURQUIM, R. F. OLIVEIRA, Estudo e Análise da Regulação de Tensão e do Suporte de PotênciaReativaemSistemasIntegrados de Transmissão de EnergiaElétrica, UTFPR, Curitiba, 2014, pp. 20 – 40.
[4] M. G. DELANHESE, Melhoria do Perfil de Tensãoem Redes de EnergiaElétrica Via AlocaçãoÓtima de Banco de Banco de Capacitores, UFTPR, CornélioProcópio, 2018, pp. 20 – 31.
[5] S.A. FILHO, Análise de ControladoresEletrônicosemSistemas de Distribuição de Energia, UNESP, IlhaSolteira, 2005, pp. 18 – 34.
[6] D. C. PINHEIRO, Eliminação de SobrecargasemSistemas de TransmissãoAtravés do Chaveamento de Ramos, UNICAMP, Campinas, 2016, pp. 21 – 23.
[7] A. BORGES, F. S ROCHA, R. R. YANGNYCZ, Modelagem de um Sistema de Transmissão de EnergiaElétrica com CompensaçãoVia FACTS, UTFPR, Curitiba, 2015, pp. 19 – 41.
[8] J. S. NATURESA, A influência de CompensadoresEstáticos de ReativosnaEstabilidade de Tensão de Sistemas de EnergiaElétrica, UNICAMP, Campinas, 2001, pp. 13 – 33.
[9] C. H. R. R. SANTOS, Influência do StatcomnaEstabilidade dos SistemasElétricos de Potência, UNIFEI, Itajubá, 2003, pp 23- 120.
[10] M. E. C. BRITO, Dispositivos de Compensação Reativa e Controle da Tensão para Redução de Perdas Técnicas em Sistemas de Distribuição, UFPE, Recife, 2015, pp. 33 – 103.
Downloads
Published
Issue
Section
License
Copyright (c) 2019 Rennivan Simões Louzeiro, Livia da Silva Oliveira, David Barbosa de Alencar, Roger Santos Koga
This work is licensed under a Creative Commons Attribution-NoDerivatives 4.0 International License.
Copyrights for articles published in IJIER journals are retained by the authors, with first publication rights granted to the journal. The journal/publisher is not responsible for subsequent uses of the work. It is the author's responsibility to bring an infringement action if so desired by the author for more visit Copyright & License.